9 Immunity
38.1143GPPNRRelease 17Repeaters ElectroMagnetic Compatibility (EMC)TS
9.1 Test configurations
This clause defines the configurations for immunity tests as follows:
– the equipment shall be tested under normal test conditions as specified in the functional standards;
– during the test, the RF output power may be reduced to a power level sufficient for establishing and maintaining the required communication link;
– the test configuration shall be as close to normal intended use as possible;
– if the equipment is part of a system, or can be connected to ancillary equipment, then it shall be acceptable to test the equipment while connected to the minimum configuration of ancillary equipment necessary to exercise the ports;
– if the equipment has a large number of ports, then a sufficient number shall be selected to simulate actual operation conditions and to ensure that all the different types of termination are tested;
– the test conditions, test configuration and mode of operation shall be recorded in the test report;
– ports which in normal operation are connected shall be connected to an ancillary equipment or to a representative piece of cable correctly terminated to simulate the input/output characteristics of the ancillary equipment. In case of repeater type 1-C, antenna ports shall be correctly terminated;
– ports which are not connected to cables during normal operation, shall not be connected to any cables for the purpose of EMC testing. Where cables have to be connected to these ports, or interconnecting cables have to be extended in length in order to exercise the EUT, precautions shall be taken to ensure that the evaluation of the EUT is not affected by the addition or extension of these cables;
– immunity tests on the entire NR repeater shall be performed by establishing communication links at the radio interface (e.g. with the mobile simulator) and the BS interface (e.g. with a BS simulator) and evaluating the [power accuracy/gain];
– immunity tests shall be performed on both the uplink and downlink paths. The tests shall also include both the radio interface and the BS interface. [Power accuracy/Gain] evaluation may be carried out at either interface, where appropriate, and the measurements for the uplink and downlink paths may be carried out as a single path looped at either the radio interface or BS interface. In case of looping is used care have to be taken that the [power accuracy/gain] doesn’t change due to looping;
– for NR repeater capable of multi-band operation, communication links shall be established in such a way that all operating band(s) are activated during the test according to the applicable test configurations in clause 4.5. Performance assessment may be done separately for each operating band.
Figure 9.1-1: Communication link set up for repeater type 1-C immunity measurement
Figure 9.1-2: Communication link set up for repeater type 2-O immunity measurement
9.2 RF electromagnetic field (80 MHz – 6000 MHz)
The test shall be performed on a representative configuration of the equipment, the associated ancillary equipment, or representative configuration of the combination of radio and ancillary equipment.
9.2.1 Definition
This test assesses the ability of radio equipment and ancillary equipment to operate as intended in the presence of a radio frequency electromagnetic field disturbance at the enclosure.
9.2.2 Test method and level
The test method shall be in accordance with IEC 61000‑4‑3 [13], which specified test methodology based on anechoic chamber. The use of reverberation chamber test method according to IEC 61000-4-21 [18], clause 6.1 and Annex D as alternative method is allowed.
The following requirements shall apply:
– The test level shall be 3 V/m amplitude modulated to a depth of 80 % by a sinusoidal audio signal of 1 kHz;
– The stepped frequency increments shall be 1 % of the momentary frequency;
– The test shall be performed over the frequency range 80 MHz – 6000 MHz; with the exception of the exclusion band for receivers (see clause 4.4.2);
– Responses in stand-alone receivers or receivers which are part of transceivers occurring at discrete frequencies which are narrow band responses, shall be disregarded, see clause 4.3;
– The frequencies selected during the test shall be recorded in the test report.
– For the test method in accordance with IEC 61000-4-3 [13], for repeater operating in FR2 the spatial exclusion zone can be chosen to protect the NR repeater’s receiver. For the frequency arrange above 690 MHz (according to the test method in ETSI EN 301 489-50 [22) the EMC RF electromagnetic field immunity requirement applies on the non-radiating faces of the repeater type 2-O, as depicted on figure 9.2.2-1..
NOTE: Depending on the BS implementation, application of the spatial exclusion to all radiating faces of the NR repeater may not allow proper execution of the RI testing. In such cases, to protect the repeater type 2-O receiver(s), exclusion bands shall be considered, as in table 4.4.2-2.
Figure 9.2.2-1: EMC RF electromagnetic field immunity requirement testing directions for NR repeater type 2-O (horizontal plane depicted) with the spatial exclusion zone applied
9.2.3 Performance criteria
NR repeater:
The performance criteria of clause 6.1 shall apply.
Ancillary equipment:
The performance criteria of clause 6.3 shall apply.
9.3 Electrostatic discharge
The test shall be performed on a representative configuration of the radio equipment, the associated ancillary equipment, or representative configuration of the combination of radio and ancillary equipment.
9.3.1 Definition
This test assesses the ability of radio equipment and ancillary equipment to operate as intended in the event of an electrostatic discharge.
9.3.2 Test method and level
The test method shall be in accordance with IEC 61000‑4‑2 [12]:
– for contact discharge, the equipment shall pass at ±4 kV;
– for air discharge shall pass at ±8 kV;
– electrostatic discharge shall be applied to all exposed surfaces of the EUT except where the user documentation specially indicates a requirement for appropriate protective measures.
9.3.3 Performance criteria
NR repeater:
The performance criteria of clause 6.2 shall apply.
Ancillary equipment:
The performance criteria of clause 6.4 shall apply.
9.4 Fast transients common mode
The test shall be performed on AC mains power input ports.
This test shall be performed on signal ports, telecommunication ports, control ports and DC power input/output ports if the cables may be longer than 3 m.
Where this test is not carried out on a port or any other ports because the manufacturer declares that it is not intended to be used with cables longer than 3 m, a list of ports which were not tested for this reason shall be included in the test report.
This test shall be performed on a representative configuration of the equipment, the associated ancillary equipment, or representative configuration of the combination of radio and ancillary equipment.
9.4.1 Definition
This test assesses the ability of radio equipment and ancillary equipment to operate as intended in the event of fast transients present on one of the input/output ports.
9.4.2 Test method and level
The test method shall be in accordance with IEC 61000‑4‑4 [14]:
– The test level for signal ports, telecommunication ports and control ports shall be 0.5 kV open circuit voltage as given in IEC 61000‑4‑4 [14];
– The test level for DC power input/output ports shall be 0.5 kV open circuit voltage as given in IEC 61000‑4‑4 [14];
– The test level for AC mains power input ports shall be 1 kV open circuit voltage as given in IEC 61000‑4‑4 [14].
9.4.3 Performance criteria
NR repeater:
The performance criteria of clause 6.2 shall apply.
Ancillary equipment:
The performance criteria of clause 6.4 shall apply.
9.5 RF common mode (0.15 MHz – 80 MHz)
The test shall be performed on AC mains power input/output ports.
This test shall be performed on signal ports, telecommunication ports, control and DC power input/output ports, which may have cables longer than 3 m.
Where this test is not carried out on a port or any other ports because the manufacturer declares that it is not intended to be used with cables longer than stated above, a list of ports which were not tested shall be included in the test report.
This test shall be performed on a representative configuration of the equipment, the associated ancillary equipment, or representative configuration of the combination of radio and ancillary equipment.
9.5.1 Definition
This test assesses the ability of radio equipment and ancillary equipment to operate as intended in the presence of a radio frequency electromagnetic disturbance.
9.5.2 Test method and level
The test method shall be in accordance with IEC 61000‑4‑6 [16]:
– The test signal shall be amplitude modulated to a depth of 80 % by a sinusoidal audio signal of 1 kHz;
– The stepped frequency increments shall be 50 kHz in the frequency range 150 kHz to 5 MHz and 1% frequency increment of the momentary frequency in the frequency range 5 MHz to 80 MHz;
– The test level shall be severity level 2 as given in IEC 61000‑4‑6 [16] corresponding to 3 V rms, at a transfer impedance of 150 Ω;
– The test shall be performed over the frequency range 150 kHz – 80 MHz;
– The injection method to be used shall be selected according to the basic standard IEC 61000-4-6 [16];
– Responses of stand-alone receivers or receivers which are part of transceivers occurring at discrete frequencies which are narrow band responses, shall be disregarded, see clause 4.3;
– The frequencies of the immunity test signal selected and used during the test shall be recorded in the test report.
9.5.3 Performance criteria
NR repeater:
The performance criteria of clause 6.1 shall apply.
Ancillary equipment:
The performance criteria of clause 6.3 shall apply.
9.6 Voltage dips and interruptions
The tests shall be performed on AC mains power input ports.
These tests shall be performed on a representative configuration of the equipment, the associated ancillary equipment, or representative configuration of the combination of radio and ancillary equipment.
9.6.1 Definition
These tests assess the ability of radio equipment and ancillary equipment to operate as intended in the event of voltage dips and interruptions present on the AC mains power input ports.
9.6.2 Test method and level
The following requirements shall apply.
The test method shall be in accordance with IEC 61000‑4‑11 [17].
The test levels shall be:
– Voltage dip: 0 % residual voltage for 0.5 cycle;
– Voltage dip: 0 % residual voltage for 1 cycle;
– Voltage dip: 70 % residual voltage for 25/30 cycles (at 50/60 Hz);
– Voltage interruption: 0 % residual voltage for 250/300 cycles (at 50/60 Hz).
9.6.3 Performance criteria
For a 0 % residual voltage dip test, the performance criteria for transient phenomena shall be applied:
– Criteria 6.2 for NR repeater
– Criteria 6.4 for ancillary equipment
For a 70% residual voltage dip test and for voltage interruption test, the following applies:
1. In the case where the equipment is fitted with or connected to a battery back-up, the following performance criteria shall be applied:
– Criteria 6.2 for NR repeater
– Criteria 6.4 for ancillary equipment
2. In the case where the equipment is powered solely from the AC mains supply (without the use of a parallel battery back-up) volatile user data may have been lost and if applicable the communication link need not to be maintained and lost functions should be recoverable by user or operator:
– No unintentional responses shall occur at the end of the test
– In the event of loss of communications link or in the event of loss of user data, this fact shall be recorded in the test report.
9.7 Surges, common and differential mode
The tests shall be performed on AC mains power input ports.
This test shall be additionally performed on telecommunication ports.
These tests shall be performed on a representative configuration of the repeater, the associated ancillary equipment, or representative configuration of the combination of radio and ancillary equipment.
9.7.1 Definition
These tests assess the ability of radio equipment and ancillary equipment to operate as intended in the event of surges being present at the AC mains power input ports and telecommunication ports.
9.7.2 Test method and level
The test method shall be in accordance with IEC 61000-4-5 [15].
The requirements and evaluation of test results given in clause 9.7.2.1 (telecommunication ports, outdoor cables), clause 9.7.2.2 (telecommunication ports, indoor cables) and clause 9.7.2.3 (AC power ports) shall apply, but no test shall be required where normal functioning cannot be achieved, because of the impact of the CDN on the EUT.
9.7.2.1 Test method for telecommunication ports directly connected to outdoor cables
The test level for telecommunications ports, intended to be directly connected to the telecommunications network via outdoor cables, shall be 1 kV line to ground as given in IEC 61000-4-5 [15]. In this case the total output impedance of the surge generator shall be in accordance with the basic standard IEC 61000-4-5 [15].
The test generator shall provide the 1.2/50 μs pulse as defined in IEC 61000-4-5 [15].
9.7.2.2 Test method for telecommunication ports connected to indoor cables
The test level for telecommunication ports, intended to be connected to indoor cables (longer than 10 m) shall be 0.5 kV line to ground. In this case the total output impedance of the surge generator shall be in accordance with the basic standard IEC 61000-4-5 [15].
The test generator shall provide the 1.2/50 μs pulse as defined in IEC 61000-4-5 [15].
9.7.2.3 Test method for AC power ports
The test level for AC power input ports shall be 2 kV line to ground, and 1 kV line to line, with the output impedance of the surge generator as given in IEC 61000-4-5 [15].
In telecommunication centres 1 kV line to ground and 0.5 kV line to line shall be used.
The test generator shall provide the 1.2/50 μs pulse as defined in IEC 61000-4-5 [15].
9.7.3 Performance criteria
NR repeater:
The performance criteria of clause 6.2 shall apply.
Ancillary equipment:
The performance criteria of clause 6.4 shall apply.